A comprehensive motor protection relay used for large LV and medium voltage 3-phase motor protection and control via multiple starting logic options
Thermal overload, earth fault, negative phase sequence, under and over voltage, phase loss, phase rotation, 5 channel over-temp protection via thermistors or RTDs
Click For More Information50x50mm Graphical LCD with start curve capture
9x LEDs
17x Digital inputs
4x Changeover contact relay outputs
5x RTC/PTC/NTC 3 wire inputs
4x CT inputs 1A or 5A (3ph + 1EF)
3x VT Inputs 100-500V ac nominal
Aux supply 80-265V ac/dc or low voltage 24-70V ac/dc
RS485 Modbus
Mini USB front port
MicroMotor (uMotor) is suitable for a variety of motor starting configurations and was designed as the smallest of our intelligent devices to provide protection and control for high density, multi-tier motor control centre (MCC) projects.
Click For More Information
The MicroMotor relay is housed within a 96x96mm flush panel-mounting DIN case with a separate din rail mounting CT module connected via a 300mm cable.
The MicroMotor can be equipped with one of several communication protocols, Modbus RS485, Profibus DP, Modbus over Ethernet
2×16 line LCD
5x Digital inputs
3x Changeover contact relay outputs
1x VT Input 100-500V ac nominal (Ph-N or Ph-Ph connection)
Aux supply 80-265V ac/dc or low voltage 24-70V ac/dc
RS485 Modbus or Profibus or Ethernet TCP/IP port
Mini USB front port
optional
1x RTC/PTC/NTC 3 wire input
Separately mounted
4x CT inputs 1A or 5A (3ph + 1EF)
The uMotor can be supplied in a package allowing the device to be DIN rail mountable to standard 35mm tophat din rail. The normal connections for power, Vref, DI/DO’s are then made at 90 degrees to the rear of the relay.
The CT connection is rated at 25mA and is designed to 5p10 at the following ratings:
10A:0.025A (10A:25mA) for motors with an expected full load current of between 2.5A to 15A
50A:0.025A (50A:25mA) for motors with an expected full load current of between 12.5A to 75A
100A:0.025A (100A:25mA) for motors with an expected full load current of between 25A to 150A
The 25mA output has some advantages in that it is still a measurement based upon a current loop and yet the normal amount of iron within the CT core for typical 5A or 1A secondary outputs, (particularly at low primary/energising currents) is not needed and therefore the physical size of a low primary CT remains very small.
If necessary the phase CTs can be double wound with the primary conductor (providing the CT aperture space permits this) in order to reduce the In rating to half.
So, a 10A:0.025mA can be suitably used as a 5A:25mA CT with two passes of the primary conductor.
A comprehensive and extensively used relay used for large LV and medium voltage 3-phase motor protection, developed primarily as a direct replacement for the older MPR2000.
Thermal overload, earth fault, negative phase sequence, under and over voltage, phase loss, phase rotation, 5 channel over-temp protection via thermistors or RTDs.
Click For More Information
192(w)x96mm(h) flush panel-mounting DIN case with phoenix type plug-in connectors
50x50mm Graphical LCD with start curve capture
9x LEDs
17x Digital inputs
4x Changeover contact relay outputs
5x RTC/PTC/NTC 3 wire inputs
4x CT inputs 1A or 5A (3ph + 1EF)
3x VT Inputs 100-500V ac nominal
Aux supply 80-265V ac/dc or low voltage 24-70V ac/dc
RS485 Modbus
Mini USB front port
P&B is a leading UK innovator of electrical protection, safety and control technologies.
Our specialist expertise and unrivalled experience is relied upon in heavy industries throughout the world to ensure the highest levels of safety and performance.